Operation

The Motor Purging and Pressurization control system has been designed for use on large electrical machines located in a hazardous location.

The system delivers a high purge rate for a given duration (as defined by machine designer and Notified Body) prior to start-up,to purge any potentially explosive gases from the machine.After purge,the system automatically switches to leakage compensation mode for normal operation. The ClosedLoop Automatic Pressurization System(CLAPS) automatically compensate for pressure variations in the machine during start-up or through temperature variations during operation. The system enables the machine to continuously operate at a set over-pressure, saving considerable time during test and commissioning,and simplifying normal operation.

Components

The system comprises the Control Unit (CU) and the Relief Valve (RLV). The Control Unit contains the pneumatic logic to monitor & control air flow, pressure and purge timing, and provides the system outputs. The RLV measures purge flow at the outlet and provides over-pressure protection for the machine through a patented magnetically-set exhaust valve with integrated spark arrestor.

The system outputs are volt-free contact closures terminated inside an Ex e junction box.

For Ex [p] dust applications, please refer to “Conditions for Safe Use” on the enclosures certificate.

Features

  • Simple Order Code One – model number defines Control Unit (CU) and Relief Valve (RLV)
  • User Selectable Settings(* default)
    5 pre-set selectable purge flow rates
    (7000/8000/10000/12000/14000 N1/min)
    1 -99* minute purge time (-0/+3 sec. tolerance)
    Suits a wide variety of machine frames sizes
  • Clear Visual Status Indication – Local indicators for “Alarm/Pressurized”, “Intermediate
    Low Pressure” and “Purging”
  • Continuous Operation through Closed Loop Automatic Pressurization System (CLAPS) – Eliminates spurious trips on start-up or load change
  • 316L Stainless Steel enclosure & fittings – Excellent resistance to corrosion for harsh environments
  • Full Compliance with Standards – Direct purge flow measurement at Relief Valve exhaust orifice
  • Global Approvals
    IECEx & ATEX certified Ex [px] to IEC/EN 60079-2. IECEx & ATEX certified Ex [p] to IEC/EN 61241-4 for dust applications.
    INMETRO certified Ex [px] & Ex [p] to ABNT NBR IEC 60079-2.

Explosion Protection

Hazardous Area classification:

+      IECEx & INMETRO Zone 1 (21), Group IIC T6 Gb

+      ATEX Category 2 G D, Zone 1 (21), Group IIC T6 Gb

+      Ambient Temperature: -20°C to +55°C

Technical Specification

Dimensions/spec. D808
Width w 41.3″ 1050mm
Height h 29.5″ 750mm
Depth d 10.3″ 262mm
Fitting f 2″ NPT (F)
CU Weight 70kg 1541b
RLV Width x 21.26″ 540mm
RLV Height y 16.14″ 410mm
RLV Depth z 11.8″ 292mm
RLV Weight 23 kg Sib

 

Enclosure & Mounting

Wall mounting lugs & spacer provided for fitting to machine.

 

Process Connections

Purge Supply: 2″ NPT (F).

Minimum Supply Line: 50mm (2″) 1.0.

Reference points & signals: 1/8″ NPT (F)

 

Compressed Air Supply: Clean Dry Air or Inert Gas. Supply

Pressure: Min 4.2barg, Max 8barg.

Supply inlet filter 501J and regulator fitted.

Minimum supply pressure to be maintained during purge.

 

Technical Data

Order Code: D808MOTORSYS-E

Description: 7XLC/ss/ET/OV/PA/PC/D808

 

Purge flow rate, user selectable to: 7,000 to 14,000 Nl/min.

Leakage Compensation Capacity: Up to 5,100 Nl/min

@ 4.2 barg inlet pressure.

 

Intrinsically safe Electronic Timer, range 1-99 mins. Battery powered

 

System outputs are volt-free contact closures terminated on Exe Junction Box, with:

 

Power= 250 Vac 4 Amp (AC15) DPNO Ex d IIC T6

Alarm = 250 Vac 4 Amp (AC15) SPCO Ex d IIC T6

Intermediate Pressure/Pre-alarm = 250 Vac 4 Amp

(AC15) SPCO Ex d IIC T6

 

Minimum pressure sensor default set at 1.5 mbarg

Range: 1.5 to 5 mbarg

Intermediate sensor/pre-alarm default set at 4 mbarg

Range: 3 to 6 mbarg

CLAPS sensor default set at 10 mbarg

Range: 10 mbarg to 15 mbarg

 

Certification/Approval

IEC Zone 1 (21) Ex [px] ia IIC T6 Gb

ATEX II 2 (2) G D Ex [px] ia IIC T6 Gb

INMETRO/TUV Zone 1 Ex [px] ia IIC T6 Gb

 

Relief Valve Lift-Off pressure setting: default 30mbarg

Minimum: 20mbarg, Maximum: 35mbarg

Options

  • Output kit for system purge in progress for D808
    Order Code: KMP-1SP0-006
  • Output kit for high pressure switch for D808
    Order Code: KMP-1SP0-007
  • Secondary low pressure switch for D808 system
    Order Code: KMP-1SP0-011